TI -2000
Active Inverter
CCC, ISO9001, RoHS, CE, SAA
>1000W
Full-Bridge Type
Sine Wave Inverter
DC/AC Inverters
-48VDC
-40~-58VDC
220VAC, 1phase
True Sine Wave
2kVA/1400W
2u
Electric Power
Telecom
450*430*90mm
JETPOWER
Plywood Case
CE
China
85044030
Product Description
TI Series 48VDC Telecom Inverter with CE Approved (1K~8K)
Snapshots:
Model: TI-2000
Capacity: 2KVA/1400W
DC Input Vol: -48V
AC Input Vol: 230VAC or 115VAC (by pass is Optional)
AC output: 230VAC or 115VAC
48VDC inverter Features:
(1) Pure sine wave output
(2) High efficiency conversion
(3) Primary DC input and secondary AC input available
(4) Tower or rack-mount convertible
(5) 2U height design
(6) High power, Low profile
(7) Advanced Microprocessor control
(8) Design Provides High Reliability and Efficiency
(9) Over load protection and alarm
(10) Low audible noise: < 55 dB
(11) EMI meet VDE0871 Class A
(12) RS 232 communication
(13) MTBR<1hrs
(14) Dry Contact alarm interface
(15) Fax/ Modem surge Suppression ports
(16) RJ45 Network surge suppression ports
Product images
Specifications for TI Series Inverter (1-8K)
Snapshots:
Model: TI-2000
Capacity: 2KVA/1400W
DC Input Vol: -48V
AC Input Vol: 230VAC or 115VAC (by pass is Optional)
AC output: 230VAC or 115VAC
48VDC inverter Features:
(1) Pure sine wave output
(2) High efficiency conversion
(3) Primary DC input and secondary AC input available
(4) Tower or rack-mount convertible
(5) 2U height design
(6) High power, Low profile
(7) Advanced Microprocessor control
(8) Design Provides High Reliability and Efficiency
(9) Over load protection and alarm
(10) Low audible noise: < 55 dB
(11) EMI meet VDE0871 Class A
(12) RS 232 communication
(13) MTBR<1hrs
(14) Dry Contact alarm interface
(15) Fax/ Modem surge Suppression ports
(16) RJ45 Network surge suppression ports
Product images
Specifications for TI Series Inverter (1-8K)
True Sine Wave Output | |||||||
Model | TI-1000 | TI-2000 | TI-3000 | TI-5000 | TI-7000 | TI-8000 | |
Structure | Low Frequency SPWM | ||||||
Capacity | 1kVA / 0.7kW | 2kVA / 1.4kW | 3kVA / 2.1kW | 5kVA /3.5kW | 7kVA /5kW | 8kVA /6kW | |
DC Input | |||||||
Normal voltage | -48Vdc | ||||||
Voltage range | -40~-57Vdc | ||||||
Wide band noise current | <10% | ||||||
Psophometric noise current | <2‰ | ||||||
AC Bypass Input (Optional) | |||||||
Normal voltage | 115V/230Vac | 230Vac | |||||
Voltage range | 80~135Vac | 160~270Vac | |||||
160~270Vac | |||||||
Frequency range | 50/60Hz±5% | ||||||
Output | |||||||
Normal voltage | 115V/230Vac | 230Vac | |||||
Voltage Stability | ±2%(Typical) | ||||||
Frequency stability | |||||||
Wave style | Sine Wave | ||||||
Overload Capacity | 110~150% for 20sec ; >150% Protect at once | ||||||
Indicators | |||||||
LCD Front panel | Battery capacity;Output voltage ;Load size . | ||||||
Audible Alarms | Battery low, overload, abnormity | ||||||
Communications | |||||||
Intelligent Interface | RS232 and contact closure signal or RS485 | ||||||
Compatible O/S | Windows XP/NT,Linux,Novell,Unix,SNMP,HTTP | ||||||
Safety | Meet UL 1012,EN 60950,EN 50091-1-1 | ||||||
EMI | Meet FCC Part 15,Class A | ||||||
EN 55022,Class A/EN 50091-2,Class A | |||||||
EMC | IEC 801-1,2,3,4,5/EN 61000-4-1,2,3,4,5 | ||||||
Environment | |||||||
Ambient Operation | 3000 Meters Max,0~40ºC,0~95% Humidity ( Non-Condensing ) | ||||||
Audible noise (1 meter from surface ) | <45dB | <60dB | |||||
Physical | |||||||
Size (D×W×H )mm | 450×430×90 | 450×430×132 | 550*430*132 | ||||
Net Weight | 15kg | 20kg | 24kg | 26kg | 45kg | 45kg |