ND110-1050
Active Inverter
CE, ISO9001
>1000W
Full-Bridge Type
Sine Wave Inverter
DC/AC Inverters
110VDC
220V, 50Hz, 1phase
5kVA/4kw
0.8
Pure Sine Wave
19" Rack Monut or Tower Mount
Single
Electric Power
Office, Air Conditioning, Servers, Railway etc
Jetpower
JETPOWER
Plywood Case
CE
China
85044030
Product Description
110VDC/AC Single Phase Electric Power Inverter(1KVA~20KVA)
ND series are specially designed for railway and electric power industry. Their latest advanced
technology suits all critical situations which are sensitive to power interference and need stable,
reliable, clean and uninterruptible true sine wave power supply.
Main Features:
(1) SPWM technology, pure sine wave output
(2) With output isolation transformer
(3) 100% Non linear load ability
(4) DC input reverse polarity protection,
(5) CPU control, advanced anti-interference technology, good electromagnetism compatibility
(6)User friendly LCD+LED display, easy to operate.
(7)Comprehensive protection: Over voltage, low voltage, short circuit, over load protection and etc
(8) Optional three working modes: AC mains first, DC inverter first, pure DC inverter
(9) Install: 19 inch rack or standalone
Specifications subject to change without prior notice.
ND series are specially designed for railway and electric power industry. Their latest advanced
technology suits all critical situations which are sensitive to power interference and need stable,
reliable, clean and uninterruptible true sine wave power supply.
Main Features:
(1) SPWM technology, pure sine wave output
(2) With output isolation transformer
(3) 100% Non linear load ability
(4) DC input reverse polarity protection,
(5) CPU control, advanced anti-interference technology, good electromagnetism compatibility
(6)User friendly LCD+LED display, easy to operate.
(7)Comprehensive protection: Over voltage, low voltage, short circuit, over load protection and etc
(8) Optional three working modes: AC mains first, DC inverter first, pure DC inverter
(9) Install: 19 inch rack or standalone
Model | ND 110-1010 | ND110-1020 | ND110-1030 | ND110-1050 | ND110-1100 | ND110-1200 | |
DC input | Rated DC input voltage (VDC) | 110 | |||||
Rated DC input current (A) | 9.09 | 19 | 27 | 45 | 91 | 182 | |
DC input voltage range (VDC) | 88~132Vdc | ||||||
Bypass | Utility AC input voltage (VAC) | 220Vac±20%, 50Hz±10% | |||||
Utility | Rated AC input voltage (A) | 4.5 | 9 | 13.5 | 22.7 | 45 | 91 |
input | Bypass transfer time (ms) | ≤4 | |||||
AC output | Rated capacity (KVA) | 1 | 2 | 3 | 5 | 10 | 20 |
Rated output power (KW) | 0.8 | 1.6 | 2.4 | 4 | 8 | 16 | |
Rated output voltage and frequency | 220VAC, 50HZ | ||||||
Rated output current (A) | 4.5 | 9 | 13.5 | 22.7 | 45 | 91 | |
Output voltage regulation (V) | 220Vac±2% | ||||||
Output frequency regulation(Hz) | 50±1% | ||||||
THD | ≤3% | ||||||
Dynamic response (load 0←→100%) | 5% | ||||||
Power factor | 0.8 | ||||||
Overload | 150%,60s | ||||||
Crest factor | 3:01 | ||||||
Efficiency at rated load | 90% | ||||||
Environment | Insulation strength (between input & output) | 1500VAC, 1min | |||||
Noise (1m) | ≤50dB | ||||||
Temperature | -10ºC~+50ºC | ||||||
Humidity | 0~90%, no condensation | ||||||
Altitude (m) | ≤2000 | ||||||
Sizes | Rack tye (W* D * H, mm) | 440*450*133 | 440*450*177 | 440*500*221.5 | N/A | N/A | |
Tower type(W*D*H,mm) | 200×480×490 | 210×612×540 | 240×540×680 | 343×630×700 | |||
Weight (kg)(Rack type) | 33 | 41 | 50 | 48 | N/A | N/A | |
Weight (kg)(Tower type) | 31 | 41 | 51 | 58 | 112 | 160 |